Description
ZW7-40.5 outdoor high-voltage vacuum circuit breaker is used for three-phase power system with ac 50Hz and voltage of 40.5kv, for breaking and closing load current, overload current and short circuit current.
Working conditions
1.the ambient air temperature: cap+ 40℃, the minimum - 30℃;
2.Altitude: 2000m(if elevation is needed, the rated insulation level shall be increased accordingly);
3.Wind pressure: not exceeding 700Pa(equivalent to 34m/s wind speed);
4.amplitude: seismic intensity 8 degrees;
5.Pollution level: level III;
6.the maximum daily temperature difference: no more than 25℃.
Model and meanings
Features and advantages
1.Vacuum arc extinguishing, strong breaking ability, long electrical life and 10,000 mechanical life;
2.simple structure, no maintenance, no long maintenance cycle; 3, good insulation performance, anti-pollution ability;
4.can be equipped with spring or electromagnetic operating mechanism, mechanical performance is reliable, frequent operation; No fire and explosion hazard;
5.Built-in current transformer with accuracy up to 0.2 level can realize three-phase interactive protection;
6.The built-in condensation controller can keep the circuit breaker running reliably under certain temperature and humidity .
Main technical parameters
No |
Item |
Unit |
Data |
||
1 |
Rated voltage |
KV |
40.5 |
||
2 |
Rated insulation level |
Power frequency withstand voltage |
dry |
95 |
|
wet |
80 |
||||
Lightning withstand voltage (peak) |
185 |
||||
3 |
Rated current |
A |
125016002000 |
||
4 |
Rated short circuit breaking current |
KA |
202531.5 |
||
5 |
Ra1ed operating sequence |
0-0.3s-CO- l 80s-CO |
|||
6 |
Operations of breaking rated short circuit breaking current |
Times |
12 |
||
7 |
Rated short circuit making current (peak) |
KA |
506380 |
||
8 |
Rated peak withstand current |
||||
9 |
Rated short time withstand current |
KA |
202531.5 |
||
10 |
Rated breaking continuous current |
S |
4 |
||
11 |
Average opening speed |
MS |
1.5±0.2 |
||
12 |
Average closing speed |
0.7±0.2 |
|||
13 |
Asynchrony of three-phase closing, opening |
S |
≤2 |
||
14 |
Jumping time during contact closed |
≤2 |
|||
15 |
Closing time |
≤150 |
|||
16 |
Divide production and time |
≤60 |
|||
17 |
Mechanical life |
Times |
10000 |
||
18 |
Rated operating voltage and auxiliary circuit voltage |
V |
DC22011024 |
||
AC22011024 |
|||||
19 |
DC rt1is1anceof eacbphaserircui1doesn01indudemurnal inductor |
UΩ |
≤100 |
||
20 |
total permissible abrasion 1hickness of moving and s1a1ic con1ac1s |
mm |
3 |
||
21 |
Weight |
kg |
800 |
Outline and mounting dimensions