Description
LW8-40.5, LW8A-40.5 series sulfur hexafluoride circuit breakers are three-phase AC 50Hz outdoor high-voltage electrical equipment, suitable for the control and protection of 40.5kV transmission and distribution system, can also be used for connection circuit breakers and open and close capacitor Banks. The product can be used with CT14 spring mechanism. The circuit breaker conforms to the national standard GB1984 -- 1989 AC high-voltage circuit breaker and the international electrotechnical commission standard IEC56, IEC6220-100 high-voltage ac circuit breaker.
The product has excellent breaking performance, USES the pressure air type arc extinguishing chamber, the electric life is long, does not replace the sulfur hexafluoride gas, the mechanical reliability is high, the mechanical life is long, can operate frequently; Each set can be equipped with 6-12 current transformers for user's choice. This product adopts the new MKZ model SF6 pointer density meter, the pressure gauge reading is not affected by the temperature change, easy to use.
Main technical parameters
Item |
Unit |
Data |
|
Rated voltage |
KV |
40.5 |
|
Rated insulation level |
Withstand voltage of 1min power frequency |
KV |
95 |
Lightning shock resistance (peak) |
KV |
185 |
|
Rated current |
A |
1600/2000 |
|
Mechanical life |
Times |
3000 |
|
Rated pressure of sulfur hexafluoride (gauge pressure at 20℃) |
Mpa |
0.45 |
|
Locking pressure (gauge pressure at 20℃) |
Mpa |
0.42 |
|
Minimum operating temperature |
℃ |
-30 |
|
Rated short circuit breaking current |
KA |
20/25/31.5 |
|
Rated short circuit shut-off current (peak) |
KA |
63/80 |
|
Rated withstand current in short circuit (heat stable current) |
KA |
25/31.5/100 |
|
Rated peak withstand current (dynamic stable current) |
KA |
63/80/100 |
|
Rated out-of-step breaking current |
KA |
63/80/100 |
|
Rated short circuit duration |
S |
4 |
|
Closing time (at rated operating voltage) |
S |
≤0.1 |
|
Switching time (at rated operating voltage) |
S |
≤0.07 |
|
Rated operating sequence |
0-0.3-C0-180S-CO |
||
Rated open and close current of a single capacitor bank |
A |
400 |
|
Weight of sulfur hexafluoride gas |
kg |
8/5 |
|
Weight of circuit breaker (including operating mechanism) |
kg |
14000/1000 |
Outline and mounting dimensions
LW8A-40.5(side-mounted) mounting dimensions
LW8A-40.5(porcelain column) mounting base size
LW8A-40.5(middle type) outline mounting size