Description
LW3-12, LW3-12 g I II II series outdoor high-pressure sulfur hexafluoride circuit breaker as sulfur hexafluoride gas arcing and a new type of outdoor high voltage electrical insulating medium. Operating mechanism ( I type) hand machine spring operation mechanism. ( II type) electromotor spring operating mechanism, ( Ill type) DC electromagnetic operating mechanism of three, all kinds of operation mechanism and circuit breaker ontology perfectly combined into a whole. Compared with other 10KV class outdoor circuit breakers, this product has obvious advantages such as simple structure, excellent arc extinguishing and insulation performance, small operation power, high rated parameters, long electrical life and long non-maintenance cycle. The use of this product can not only reduce the floor area. Reduce the project cost and eliminate the fire hazard, and can greatly improve the reliability of the power system.
The circuit breaker has all the functions of the basic circuit breaker, and the coincidence controller or section controller is used to constitute the smart circuit breaker. Cooperate with PT and reclosing controller (subsection controller), it has many functions such as closing on current control, overcurrent protection, short-circuit quick-break three-section compound protection and 1-3 reclosing, small current grounding protection, wired remote control and wireless remote control under bar, and the controller parameters can be set continuously. It is an ideal choice for substation, off-site scatter switch and simple metering switch.
Main technical parameters
Item |
Unit |
Data |
|||
Rated voltage |
KV |
10 |
|||
Maximum operating voltage |
KV |
12 |
|||
Rated insulation level (when 0.25mpa, 20°C) |
Lightning shock pressure withstand full wave |
KV |
75 |
||
Withstand voltage of 1 min power frequency |
KV |
42 |
|||
Rain withstand test |
KV |
34 |
|||
Reverse impact resistance |
KV |
85 |
|||
Insulation level under zero gauge pressure |
Withstand voltage of 1 min power frequency |
KV |
30 |
||
Anti-phase pressure resistance of 1 min |
KV |
30 |
|||
5min maximum phase voltage |
KV |
9 |
|||
Rated current |
A |
400,630 |
|||
Rated short circuit breaking current |
KA |
6.3 8 12.5 |
|||
Out-of-phase earth rec losing switching current |
KA |
5.5 7.1 10.9 |
|||
Open current under zero gauge pressure |
A |
400 630 |
|||
Rated operating sequence |
0-0.3s-C0-180s-CO |
||||
Rated closing current (peak) |
KA |
16 20 31.5 |
|||
Rated dynamic stability current (peak) |
KA |
16 20 31.5 |
|||
Rated thermal stability current |
KA |
6.3 8 12.5 |
|||
Stable heat stable time |
s |
4 |
|||
Just close speed |
m/s |
2.6±0.2 |
|||
Just points speed |
m/s |
2.6±0.2 |
|||
Proper closing time II Type Ill Type |
s |
≤0.06 |
|||
Proper closing time |
I Type |
s |
≤0.06 |
||
II Type Ill Type |
s |
≤0.04 |
|||
Rated working pressure |
Mpa |
0.35 (20°C) |
|||
Minimum working pressure |
Mpa |
0.25 (2°C) |
|||
In a flat rate |
% |
<0.01 |
|||
Mechanical stability (continuous integration) operation |
Times |
6000 |
|||
Weight |
I Type |
Kg |
122 |
||
II Type |
Kg |
30 |
|||
Ill Type |
Kg |
132 |
|||
SF6 gas moisture content |
PPM |
≤150 |
Outline and mounting dimensions