Description
ZW6-12/630-16(20) outdoor vacuum circuit breaker is suitable for three-phase power system with l 2kV and below, ac 50Hz. It is mainly used for dividing agricultural network and urban network, combining load current, overload current and short-circuit current. It can also be used in other similar places, and can also be used as a block switch of 12kV class power grid in urban areas.
Working conditions
1. Ambient air temperature: upper limit +40'C, lower limit -40'C;
2.Altitude: <2000m;
3. Relative humidity: daily average is no more than 95%, and monthly average is no more than 90%;
4. Wind pressure: not exceeding 700Pa(equivalent to the wind speed of 34m/s);
5. Air pollution level is grade IV according to GB5582;
6. Earthquake intensity does not exceed 8 degrees .
Model and meanings
Main technical parameters
no |
Item |
Unit |
Data |
||
1 |
Rated voltage |
kV |
12 |
||
2 |
Rated insulation level |
Power frequency withstand voltage |
dry |
kV |
42 |
Wet (to ground) |
34 |
||||
Lightning shock resistance (peak) |
75 |
||||
3 |
Rated current |
A |
630 |
||
4 |
Rated frequency |
Hz |
50 |
||
5 |
Rated short circuit breaking current |
kA |
12.5, 16, 20 |
||
6 |
Rated short circuit shut-off current |
31.5, 40, 50 |
|||
7 |
Rated peak withstand current |
31.5, 50, 50 |
|||
8 |
Rated short - term withstand current |
12.5, 16, 20 |
|||
9 |
Operating sequence |
Times |
0-0.3s-C0-180s-CO |
||
10 |
Rated number of short circuit current breaking |
30 |
|||
11 |
Mechanical life |
10000 |
|||
12 |
Rated operating voltage with CT spring operating mechanism |
V |
DC24, 48V, AC DC110V, 220V |
||
13 |
Contact allows wear thickness |
mm |
3 |
||
14 |
Rated current of overcurrent trip |
A |
5 |
||
15 |
Weight |
kg |
130(standard) |
Outline dimensions