Description
ZW10-12 outdoor high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) for a period of 12kV, rated voltage of the three-phase ac 50 Hz outdoor distribution equipment, mainly used in site, the city network, railway, port and mine and power distribution system, especially suitable for outdoor overhead line, open and close of electric power system load current, overload current and short circuit current, switching and protection of power grids.
Model and meanings
Main technical parameters
No |
Item |
Unit |
Data |
||
1 |
Rated voltage |
kV |
12 |
||
2 |
Rated current |
A |
630 1250 |
||
3 |
Rated frequency |
Hz |
50 |
||
4 |
Rated short circuit breaking current |
kA |
12.5 |
16 |
20 |
5 |
Rated peak withstand current (peak) |
kA |
31.5 |
40 |
50 |
6 |
Rated short term withstand current (4s) |
kA |
12.5 |
16 |
20 |
7 |
Rated short circuit shut-off current (peak) |
kA |
31.5 |
40 |
50 |
8 |
Rated number of short circuit breaking current |
Times |
30 |
||
9 |
Mechanical life |
Times |
10000 |
||
10 |
Power frequency withstand voltage (1min) |
kV |
42 |
||
11 |
Lightning shock withstand voltage (peak) |
kV |
75 |
||
12 |
Withstand voltage power frequency of secondary loop tor 1min |
kV |
2 |
||
13 |
Weight |
kg |
150 |
Outline and mounting dimensions